IND II31-60K Industrial Power Supply 3 Phase Uninterruptible Power Online UPS Double Conversion For Medical Telecom

Place of Origin China
Brand Name Visench
Model Number II31-60K
Minimum Order Quantity 1
Packaging Details Carton
Delivery Time 30days
Supply Ability 10000pcs/month

Contact me for free samples and coupons.

WhatsAPP:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Environment Humidity 5 - 95%, No Condensation Efficiency ≥ 90%
Overload Capacity 111–125%: 10 Mins, 126–150%: 1 Minute Altitude ≤ 1000m
Display LCD/LED Humidity 20-90%
Rated Capacity 20KVA-200KVA Transfer Time 0ms
Communication Interface RS232/USB Conversion Time 0ms
Size 533*560*1101mm Battery Quantity 384VDC
Eco Mode 99% Phase Single Phase
Input Frequency 50/ 60Hz
Highlight

Industrial Power Supply UPS

,

3 Phase Uninterruptible Power Online UPS

,

Online UPS For Medical Telecom

Leave a Message
Product Description

Low Frequency Online UPS

TD Series (three-three phase)

 

PRODUCT FEATURES

 

1. Advanced DSP digital control technology

2. LCD+LED display

3. With output isolated transformer

4. DC cold start function

5. Frequency self-adaptive system

6. Special short-circuit protection design

7. Intelligent mobile monitoring cards are supported to monitor UPS data in real time through mobile apps.

8.Equipped with three output isolation transformers, to meet the three-phase 100% unbalanced output.

 

PARAMETER                              
Model TD33 10KVA TD33 15KVA TD33 20KVA TD33 30KVA TD33 40KVA TD33 60KVA TD33 80KVA TD33 100KVA TD33 120KVA TD33 160KVA TD33 200KVA TD33 250KVA TD33 300KVA TD33 400KVA TD33 500KVA
Rated Power   10kVA/ 8kW 15kVA/ 12kW 20kVA/ 16kW 30kVA/ 24kW 40kVA/ 32kW 60kVA/ 48kW 80kVA/ 64kW 100kVA/ 80kW 120kVA/ 96kW 160kVA/ 128kW 200kVA/ 160kW 250kVA/ 200kW 300kVA/ 240kW 400kVA/ 320kW 500kVA/ 400kW
Main Input Rated Voltage and Range 380Vac ±25%
Input Form 3P4W+G
Frequency Range 40Hz-70Hz (settable)
Bypass Input Rated Voltage and Range 380Vac ±25%
Input Form 3P4W+G
Output Rated Voltage 380Vac ±25% (line voltage)
Output Form 3P4W+G
Static Voltage Accuracy ±2%
Dynamic Voltage Transient ≤9%
Distortion of output voltage waveform ≤3%(liner),≤8%(non-liner) ≤3%(liner),≤5%(non-liner)
Power Factor 0.8
Output Frequency 50Hz/60Hz
Output Overload 105%±5%≤ Load: Overload warning;
105%±5%<Load≤125%±5%: Convert to bypass output after 2 mins; 125%±5%<Load≤150%±5%: Convert to bypass output after 30s;
Load>150%±5%: Convert to bypass output after 500ms.
110%≥30mins; 125%≥10mins; 150%≥1min
Battery Rated Voltage 192Vdc 384Vdc 480Vdc 768Vdc
Dimension (LxWxH) mm 830x455x1055 830x515x1135 800x700x1600 880x850x1650 870x1300x1850 1420x908x1650 1630x1026x1902 2100x1100x2000
Weight 218kg 208kg 208kg 243kg 309kg 506.5kg 521.5kg 800kg 800kg 1099kg 1243kg 1200kg 1240kg 2600kg 3660kg